online rack-mounted ups 1-3K
1kVA 2kVA 3kVA Rack-mounted Online UPS | 900W-2700W19" Rack Mount
LBT Online Rack-mounted UPS is a new type high-frequencyonline UPS. Adopts advanced DSP digital control technology to effectivelyimprove product performance and system reliability, and higher power densitysmall size, light weight and high work efficiency. Effectively solve powerproblems such as power cut-off, Grid over voltage / low voltage, voltageinstantaneous drop, amplitude reduction, high voltage pulse, surge voltage,harmonic distortion, clutter interference, frequency fluctuation and providebest power for load.
Performance:
• DSP full digital control technology, pure online doubleconversion architecture, with strong carrying capacity
• Adopt standard cabinet,and the power distributionsystem is integrated inside the cabinet, which is convenient to install andsaves user’s investment
• Input power factor up to 0.99, low harmonic current,environmental protection, high efficiency and energy saving
• Wide input voltage range, 50Hz/60Hz grid systemadaptive, suitable for various environmental grids
• “N+X” wireless parallel redundancy technology, it iseasy to set the number of redundant parallel units through the LCD screen; allmodules support hot swap operation for easy maintenance
• Advanced battery intelligent management technology(automatic floating charge switching, battery pack temperature compensation,etc.) to effectively extend battery life
• With distributed bypass power supply, each module hasbuilt- in automatic bypass switch and corresponding bypass current sharinginductor, which provides good current sharing of system bypass power supply
• Parallel modules share the same battery pack, savinguser battery investment
• With emergency shutdown (EPO) switch and remoteemergency shutdown (REPO) function
• Perfect software and hardware protection functions(C-level lightning protection, air-opening, Fuse, hardware protection, softwareprotection), super self-diagnosis function, rich history query
• Large LCD touch widescreen display for a friendlyhuman- machine interface
• Rich communication interface, including RS232, RS485,USB, dry contact, and SNMP (optional) card
• Different external batteries can be selected accordingto user needs (32/34/36/38/40 pcs)
• Support battery cold start and city power self-startfunction to meet user needs With maintenance bypass, when there is anemergency, you can switch to the maintenance bypass power supply, and themaintenance personnel can safely perform online maintenance
• Each module adopts an independent control system. TheUPS module is independently controlled according to the shared information.After the faulty module fails, it can be disconnected from the parallel systemimmediately, which does not cause harm to the parallel system

Model item
1KR
1KRS
2KR
2KRS
3KR
3KRS
6KRS
10KRS
Rated power
1000VA/900W
2000VA/1800W
3000VA/2700W
6kVA/5.4kW
10kVA/9kW
AC Input
Input system
Single phase (L/N+PE)
Nominal voltage
HV: 208/220/230/240Vac
LV:100/110/120/127Vac
Frequency
50/60Hz
Voltage range
HV:110~285VAC±5VAC
LV: 55-145Vac±3VAC
Frequency range
(40~70)±0.5Hz
Input power factor
>0.99
Bypass Voltage Range
HV: 180~265VAC×(1±3%)
LV: 80~140VAC×(1±3%)
Battery
Input
Nominal Voltage
24V
24V/36V
48V
48V/72V
72V
72V/96V
192V/240V
Battery Capacity & Quantity
12V/7AH
x 2pcs
External
12V/7AH
x 4pcs
External
12V/7AH
x 6pcs
External
External
Backup Time
Half loaded≥6minutes,
Full loaded ≥2minutes(standard)
Dependent on the capacity of external batteries
Battery charger time
Charger to 90% battery capacity in 5 hours(standard)
Dependent on the capacity of external batteries (long backup time)
AC Output
Output wiring system
Single phase (L/N+PE)
Inverter Mode
Output voltage
HV:200V/208/220/230/240Vac±2%
LV:100/110/120/127Vac±2%
Waveform
Sine Wave
Harmonic Distortion
THD<2% (linear load)
THD<7% (nonlinear load)
Output frequency
50/60±4Hz (Sync mode)
50/60Hz±1% (Fix Freq. mode)
Overload capability
105~125%≥ 60s,126~150%≥30s The recover point is 70%
Transfer time
Battery <-> Line Mode :0ms
Efficiency
Line Mode
HV:86%
LV:86%
HV:88%
LV:86%
HV:89%
LV:87%
HV:92%
LV:88%
HV:93%
LV:89%
Battery Mode
HV&LV:85%
HV&LV:86%
HV&LV:87%
Communications
RS232 RS485(optional), Dry contact(optional), Network Card(Option)
Alarm Function
AC/DC input under abnormal, overload condition and Inverter problems
Protection Function
AC input or output above or below the range of voltage, overload, over temperature and short circuit protection
Noise
<50dB
<55dB