  • online ups 6-10K

    6kVA-10kVA Single Phase Online UPS | 5.4kW-9kW DoubleConversion 230V

    LBT Online UPS is a new type high-frequency online UPS.Adopts advanced DSP digital control technology to effectively improve productperformance and system reliability, and higher power density small size, lightweight and high work efficiency. Effectively solve power problems such as powercut-off, Grid over voltage / low voltage, voltage instantaneous drop, amplitudereduction, high voltage pulse, surge voltage, harmonic distortion, clutterinterference, frequency fluctuation and provide best power for load.

      

    Performance:

    • DSP full digital control technology, pure online doubleconversion architecture, with strong carrying capacity

    • Adopt standard cabinet,and the power distributionsystem is integrated inside the cabinet, which is convenient to install andsaves user’s investment

    • Input power factor up to 0.99, low harmonic current,environmental protection, high efficiency and energy saving

    • Wide input voltage range, 50Hz/60Hz grid systemadaptive, suitable for various environmental grids

    • “N+X” wireless parallel redundancy technology, it iseasy to set the number of redundant parallel units through the LCD screen; allmodules support hot swap operation for easy maintenance

    • Advanced battery intelligent management technology(automatic floating charge switching, battery pack temperature compensation,etc.) to effectively extend battery life

    • With distributed bypass power supply, each module hasbuilt- in automatic bypass switch and corresponding bypass current sharinginductor, which provides good current sharing of system bypass power supply

    • Parallel modules share the same battery pack, savinguser battery investment

    • With emergency shutdown (EPO) switch and remoteemergency shutdown (REPO) function

    • Perfect software and hardware protection functions(C-level lightning protection, air-opening, Fuse, hardware protection, softwareprotection), super self-diagnosis function, rich history query

    • Large LCD touch widescreen display for a friendlyhuman- machine interface

    • Rich communication interface, including RS232, RS485,USB, dry contact, and SNMP (optional) card

    • Different external batteries can be selected accordingto user needs (32/34/36/38/40 pcs)

    • Support battery cold start and city power self-startfunction to meet user needs With maintenance bypass, when there is anemergency, you can switch to the maintenance bypass power supply, and themaintenance personnel can safely perform online maintenance

    • Each module adopts an independent control system. TheUPS module is independently controlled according to the shared information.After the faulty module fails, it can be disconnected from the parallel systemimmediately, which does not cause harm to the parallel system

     

     

    Model item

    1K

    1KS

    2K

    2KS

    3K

    3KS

    6K

    6KS

    10K

    10KS

    Rated power

    1000VA/900W

    2000VA/1800W

    3000VA/2700W

    6kVA/5.4kW

    10kVA/9kW

    AC Input

    Input system

    Single phase (L/N+PE)

    Nominal voltage

    HV: 208/220/230/240Vac

    LV:100/110/120/127Vac

    Frequency

    50/60Hz

    Voltage   range

    HV: 110~285VAC±5VAC

    LV: 55-145Vac±3VAC

    Frequency range

    (40~70)±0.5Hz

    Input power factor

    >0.99

    Bypass Voltage Range  

    HV: 180~265VAC×(1±3%)

    LV: 80~140VAC×(1±3%)

     

     

    Battery

    Input

    Nominal Voltage

    24V

    24V/36V

    (customizable)

    48V

    48V/72V

    72V

    72V/96V

    144/192V

    192V

    192V/240V

    Battery Capacity   & Quantity

    12V/7AH

    x 2pcs

    External

    12V/7AH

    x 4pcs

    External

    12V/7AH

    x 6pcs

    External

    12V/7AH   x 12/16pcs

    External

    12V/7AH

    x16/20pcs

    External

    Backup Time

    Half loaded≥8minutes,

    Full loaded   ≥3minutes(standard)

    Half loaded≥6minutes,

    Full loaded ≥3minutes(standard)

    Battery charger time

    Charger to 90%   battery capacity in 5 hours(standard) Dependent on the capacity of external   batteries (long backup time)

     

     

     

    AC Output

    Output wiring system

    Single phase (L/N+PE)

    Inverter Mode

    Output voltage

    HV:200V/208/220/230/240Vac±2%

    LV:100/110/120/127Vac±2%

    Waveform

    Sine Wave 

    Harmonic Distortion

    THD<2% (linear   load) 

    THD<7% (nonlinear   load)

    Output frequency

    50/60±4Hz (Sync mode)

    50/60Hz±1% (Fix   Freq. mode)

    Overload capability

    105~125%≥ 60s,126~150%≥30s   The recover point is 70%

    Transfer time

    Battery <->   Line   Mode :0ms

    Efficiency

    Line Mode

    HV:86%

    LV:86%

    HV:88%

    LV:86%

    HV:89%

    LV:87%

    HV:92%

    LV:88%

    HV:93%

    LV:89%

    Battery Mode

    HV&LV:85%

    HV&LV:86%

    HV&LV:87%

    Communications

    RS232   RS485(optional), Dry contact(optional), Network Card(Option)

    Alarm Function

    AC/DC input under   abnormal, overload condition and Inverter problems

    Protection Function

    AC input or output   above or below the range of voltage, overload, over temperature and short   circuit protection

    Noise

    <50dB

    <55dB

     

     