全国服务热线:180-3343-9655

 

  • modular ups 30KW 30K-300K

    30kVA-300kVA Modular ThreePhase Online UPS | 30kW Module 3/3 PF 1.0

    LBT mpModular series adopts advanced “N+X” wireless parallel redundancy technology,which can support 4 parallel connections. The system is easy to update,dilatation and maintain, has excellent electrical performance, high systemavailability, perfect software and hardware protection. Including powermodules, monitoring modules, power distribution modules, maintenance bypassswitches, and output switches, providing safe and reliable power protection forvarieties of loads.

     

    Performance:

    • DSP full digital control technology, pure online doubleconversion architecture, with strong carrying capacity

    • Adopt standard cabinet,and the power distributionsystem is integrated inside the cabinet, which is convenient to install andsaves user’s investment

    • Input power factor up to 0.99, low harmonic current,environmental protection, high efficiency and energy saving

    • Wide input voltage range, 50Hz/60Hz grid systemadaptive, suitable for various environmental grids

    • “N+X” wireless parallel redundancy technology, it iseasy to set the number of redundant parallel units through the LCD screen; allmodules support hot swap operation for easy maintenance

    • Advanced battery intelligent management technology(automatic floating charge switching, battery pack temperature compensation,etc.) to effectively extend battery life

    • With distributed bypass power supply, each module hasbuilt- in automatic bypass switch and corresponding bypass current sharinginductor, which provides good current sharing of system bypass power supply

    • Parallel modules share the same battery pack, savinguser battery investment

    • With emergency shutdown (EPO) switch and remoteemergency shutdown (REPO) function

    • Perfect software and hardware protection functions(C-level lightning protection, air-opening, Fuse, hardware protection, softwareprotection), super self-diagnosis function, rich history query

    • Large LCD touch widescreen display for a friendlyhuman- machine interface

    • Rich communication interface, including RS232, RS485,USB, dry contact, and SNMP (optional) card

    • Different external batteries can be selected accordingto user needs (32/34/36/38/40 pcs)

    • Support battery cold start and city power self-startfunction to meet user needs With maintenance bypass, when there is anemergency, you can switch to the maintenance bypass power supply, and themaintenance personnel can safely perform online maintenance

    • Each module adopts an independent control system. TheUPS module is independently controlled according to the shared information.After the faulty module fails, it can be disconnected from the parallel systemimmediately, which does not cause harm to the parallel system

       



     

     

     

    Model(maximum   capacity)

    MP100K/MP150K/MP200kVA/MP300kVA/MP400kVA/MP500kVA/MP600kVA/MP720kVA

    Capacity

    UPS   cabinet

    20-200kVA/30-300kVA/40-400kVA/50-600kVA/60-720kVA

    Module

    20kVA/30kVA/40kVA/50kVA/60kVA

    Main road input

    Input mode

    Three-phase,   four-wire + grounding

    Rated voltage

    380/400V/415VAC

    Voltage range

    138-485VAC;   305-485VAC (not decreased); 138-305 VAC)

    Frequency range

    40~70Hz

    Power factor

    0.99

    Input current   harmonics

    3%   (100%   linear load)

    Bypass input

    Input voltage

    380/400/415VAC

    Bypass range

    Upper bypass   protection voltage: +25% (optional +5%, +10%, +20%)

    Lower bypass   protection voltage limit: -45% (optional -20%, -30%)

    The wiring system

    Three phase five   line

    Bypass    synchronization tracking range (Hz)

    50/60±10%

    Power Walking In

    Support

    Bypass anti-port

    Support

    Generator access

    Support

    Output

    Rated voltage

    380/400/415VAC±1%

    Power factor

    0.9/1.0

    Voltage accuracy

    ±1%

    Output    frequency

    Main   mode

    Synchronized with   input; the output frequency is 50/60 (±0.2%   Hz when the mainmax exceeds ±10% (±1%, ±2%, ±4%, ±5% are set)

    Battery   mode

    50/60(±0.1%)Hz

    The load peak ratio

    3:1

    Switching period

    Municipal mode to   bypass mode: 0ms (tracking); 

    municipal mode to   battery mode: 0ms

    Overload capacity

    Load≤110%, 60min, 125%, maintained for 10min, and 150% for   1min

    Output voltage   distortion

    ≤2% linear load

    With<4% nonlinear   load

    Efficiency

    Normal mode

    ≥96.5%

    Communication   interface

    UPS cabinet

    RS232, RS485,2   Intelligent Slot (smart card slots), dry contact

    Battery

    Battery voltage

    ±180~±300Vdc (optional in 30~50 sections)

    Work environment

    Working temperature

    -10℃~45°℃

    Relative humidity

    0~95%   with no   condensation

    Storage temperature

    -20℃~65°℃

    Altitude

    <1500m

    Noise (DB)

    <70 (at 1 m)

    Physical    characteristics

    20/30/40kVA
       3 Module cabinet

    20/30/40kVA
       5/6 Module cabinet

    20/30/40kVA
       10 Module cabinet

    50/60kVA
       10/12 module cabinet

    Size   W×D×
       H(mm)

    UPS   system   cabinet

    600×840×1400

    600×840×1400

    600×1100×2000

    1200×850×2000

    Module

    440×580×130(86)

    440×620×130

    Weight   (Kg)

    UPS   system   cabinet

    157

    169

    306(245)

    435/510

    Module

    32(21)

    33

    Executive standards

    Executive standards

    CE,   EN/EC 62040-2,EN/IEC 62040-1-1,YD/T2165-2017

     

     