+86 18033439936
-
modular ups 60KW 60K-600K
180kVA-600kVA Modular ThreePhase Online UPS | 60kW Module 3/3 PF 1.0
LBT mpModular series adopts advanced “N+X” wireless parallel redundancy technology,which can support 4 parallel connections. The system is easy to update,dilatation and maintain, has excellent electrical performance, high systemavailability, perfect software and hardware protection. Including powermodules, monitoring modules, power distribution modules, maintenance bypassswitches, and output switches, providing safe and reliable power protection forvarieties of loads.
Performance:
• DSP full digital control technology, pure online doubleconversion architecture, with strong carrying capacity
• Adopt standard cabinet,and the power distributionsystem is integrated inside the cabinet, which is convenient to install andsaves user’s investment
• Input power factor up to 0.99, low harmonic current,environmental protection, high efficiency and energy saving
• Wide input voltage range, 50Hz/60Hz grid systemadaptive, suitable for various environmental grids
• “N+X” wireless parallel redundancy technology, it iseasy to set the number of redundant parallel units through the LCD screen; allmodules support hot swap operation for easy maintenance
• Advanced battery intelligent management technology(automatic floating charge switching, battery pack temperature compensation,etc.) to effectively extend battery life
• With distributed bypass power supply, each module hasbuilt- in automatic bypass switch and corresponding bypass current sharinginductor, which provides good current sharing of system bypass power supply
• Parallel modules share the same battery pack, savinguser battery investment
• With emergency shutdown (EPO) switch and remoteemergency shutdown (REPO) function
• Perfect software and hardware protection functions(C-level lightning protection, air-opening, Fuse, hardware protection, softwareprotection), super self-diagnosis function, rich history query
• Large LCD touch widescreen display for a friendlyhuman- machine interface
• Rich communication interface, including RS232, RS485,USB, dry contact, and SNMP (optional) card
• Different external batteries can be selected accordingto user needs (32/34/36/38/40 pcs)
• Support battery cold start and city power self-startfunction to meet user needs With maintenance bypass, when there is anemergency, you can switch to the maintenance bypass power supply, and themaintenance personnel can safely perform online maintenance
• Each module adopts an independent control system. TheUPS module is independently controlled according to the shared information.After the faulty module fails, it can be disconnected from the parallel systemimmediately, which does not cause harm to the parallel system

Model(maximum capacity)
MP100K/MP150K/MP200kVA/MP300kVA/MP400kVA/MP500kVA/MP600kVA/MP720kVA
Capacity
UPS cabinet
20-200kVA/30-300kVA/40-400kVA/50-600kVA/60-720kVA
Module
20kVA/30kVA/40kVA/50kVA/60kVA
Main road input
Input mode
Three-phase, four-wire + grounding
Rated voltage
380/400V/415VAC
Voltage range
138-485VAC; 305-485VAC (not decreased); 138-305 VAC)
Frequency range
40~70Hz
Power factor
0.99
Input current harmonics
3% (100% linear load)
Bypass input
Input voltage
380/400/415VAC
Bypass range
Upper bypass protection voltage: +25% (optional +5%, +10%, +20%)
Lower bypass protection voltage limit: -45% (optional -20%, -30%)
The wiring system
Three phase five line
Bypass synchronization tracking range (Hz)
50/60±10%
Power Walking In
Support
Bypass anti-port
Support
Generator access
Support
Output
Rated voltage
380/400/415VAC±1%
Power factor
0.9/1.0
Voltage accuracy
±1%
Output frequency
Main mode
Synchronized with input; the output frequency is 50/60 (±0.2% Hz when the mainmax exceeds ±10% (±1%, ±2%, ±4%, ±5% are set)
Battery mode
50/60(±0.1%)Hz
The load peak ratio
3:1
Switching period
Municipal mode to bypass mode: 0ms (tracking);
municipal mode to battery mode: 0ms
Overload capacity
Load≤110%, 60min, 125%, maintained for 10min, and 150% for 1min
Output voltage distortion
≤2% linear load
With<4% nonlinear load
Efficiency
Normal mode
≥96.5%
Communication interface
UPS cabinet
RS232, RS485,2 Intelligent Slot (smart card slots), dry contact
Battery
Battery voltage
±180~±300Vdc (optional in 30~50 sections)
Work environment
Working temperature
-10℃~45°℃
Relative humidity
0~95% with no condensation
Storage temperature
-20℃~65°℃
Altitude
<1500m
Noise (DB)
<70 (at 1 m)
Physical characteristics
20/30/40kVA
3 Module cabinet20/30/40kVA
5/6 Module cabinet20/30/40kVA
10 Module cabinet50/60kVA
10/12 module cabinetSize W×D×
H(mm)UPS system cabinet
600×840×1400
600×840×1400
600×1100×2000
1200×850×2000
Module
440×580×130(86)
440×620×130
Weight (Kg)
UPS system cabinet
157
169
306(245)
435/510
Module
32(21)
33
Executive standards
Executive standards
CE, EN/EC 62040-2,EN/IEC 62040-1-1,YD/T2165-2017